EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Alarm LED Latch
The tri-color LED on the face of the detector turns red when in alarm and can be configured to be either latching
or non-latching. If latching is selected, following a fire detection, the LED will stay on until the detector is reset
from the point display for the detector in the S
3
software. The default is non-latching.
Fault LED Latch
The tri-color LED on the face of the detector turns yellow when a fault is present (fire over-rides fault) and can
be configured to be either latching or non-latching. If latching is selected, following a fire detection, the LED will
stay on until the detector is reset from the point display for the detector in the S
3
software. The default is non-
latching.
PV Deadband
A field is provided to enter the desired PV (Process Variable) Deadband.
Normally all values are transmitted to the controller every five seconds; If the PV changes more than the entered
percentage before the five second report time arrives, an immediate message is sent with the current values.
MIR H2 X3302 • ALARM LED LATCH