13-68
EQP LOGIC EDITOR
Version 6.0
Item 11 - Time and Date of Configuration
The time and date of the configuration information is saved in this variable.
Item 12 - Unique Configuration Number
Each configuration will be assigned a unique number, which can be used to identify the configuration.
Item 13 - Configuration Port Baud Rate
Serial baud rate for the controller configuration port is set with this variable. A code is used to represent each
rate.
Baud Rate Codes
Code Speed
1 2400
2 4800
3 9600*
4 19.2K
5 38.4K
6 57.6K
7 115.2K
* Default rate
Item 14 - Configuration Port Parity
Controller configuration port parity setting is set with this variable. A code is used to represent each type.
Parity
Code Type
1 None
2 Odd
3 Even
Item 15 - LON Address
Each device on the LON network must have a unique address. Valid controller addresses are in the range of 1
to 4. Field device addresses are in the range of 5 to 250.
Controller LON Address
Primary controllers will set this variable to 1 while secondary controllers will have a value of 2. User logic and
external interfaces can use this variable to determine which controller is currently the master. Host configuration
software need not write to this item.
Item 16 - Option Board Type
This variable defines the type of option board installed.
Option Board Types
Value Description
1 No Option Board Installed
2 ControlNet
DEVICE ITEM NUMBER DESCRIPTIONS