13-69
EQP LOGIC EDITOR
Version 6.0
Item 17 - Current Time and Date
The controller real time clock can be set or read with this variable.
Item 18 - User Name
Name of the user that was logged into S
3
when the project was built.
Item 19 - ControlNet MAC Address
The ControlNet MAC address is set with this variable. Allowable values range from 1 to 99.
Item 20 - Serial Port 1 Protocol
The second serial port protocol is set with this variable.
Serial Port Protocols
Value Description
1
Port not used
2
Modbus Slave
3
Modbus Master
Item 21 - Serial Port 1 Baud Rate
Serial baud rate for the controller RS485 serial port is set with this variable. The default baud rate is 9600.
Baud Rate Codes
Code Speed
1 2400
2 4800
3 9600
4 19.2K
5 38.4K
6 57.6K
7 115.2K
Item 22 - Serial Port 1 Parity
The controller second serial port parity setting is set with this variable. The default parity is “None”.
Item 23 - Serial Port 1 Address
The address field is only used for Modbus protocol. Valid Modbus addresses are in the range from 1 to 247. The
default address is 1.
Item 24 - Allow LON Point Disabling
If this variable is set true, LON device disabling will be allowed. This feature has not been implemented, at this
time disabling is always allowed.
DEVICE ITEM NUMBER DESCRIPTIONS