Det-tronics S3 Graphics Manual de usuario Pagina 211

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 327
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 210
12-96
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Description
This field provides an area to describe the function of each relay. Adding this optional information can make
troubleshooting and startup easier.
Com Fail Mode
Each of the 8 relays can be individually configured to respond in one of three ways in the unlikely event of a
complete loss of communications with the EQP controller.
The three selections are as follows:
Failed Off: Relay coil de-energizes
Failed On: Relay coil energizes
Hold Last State
: Relay coil stays energized or de-energized as per its last valid command from the EQP
controller.
Alarms
Selecting this button opens the “Alarms to Monitor...” dialog box.
This scrolling list displays the alarms and events related to the device that can be configured to be monitored
by S
3
.
RELAY MODULE • COM FAILED MODE
Vista de pagina 210