12-28
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Oi Configuration
The frequency of Oi testing can be adjusted between once a minute as maximum and up to once every ten
minutes as a minimum. There is also a checkbox for automatic operation.
The number of failed Oi tests needed to generate a fault can also be adjusted within a range of 1 to 30. Test
failures can sometimes be generated during heavy rain or other environmental conditions thus requiring this
parameter to be flexible.
Sensitivity
Dense fog, rain as well as certain gases and vapors can absorb IR radiation and reduce the sensitivity of the
detector.
The sensitivity of the detector can be adjusted to any one of four settings using the slider control as shown
above.
X9800 • Oi CONFIGURATION