12-81
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
Intelligent Protection Module (IPM)
8 channel input/output module for 24 Vdc discrete field devices
The Intelligent Protection Module (IPM) is a part of the Det-Tronics Eagle Quantum Premier (EQP) System that is
specially designed to monitor, supervise and control one fire suppression hazard.
The IPM is designed to provide continuous and automated local area fire protection, while monitoring system
operation through continuous supervision of its Inputs/Outputs and Local Operating Network/Signalling Line
Circuit (LON/SLC) connection to the EQP controller.
In addition the module contains a unique “embedded logic program” that if enabled during configuration allows
the IPM to perform local area protection in a “back-up mode” without controller interaction. The IPM utilizes eight
pre-configured Input/Output (I/O) channels to perform its monitoring, supervision and mitigation functions.
Inputs
On the input side, three supervised channels provide the following connections:
Channel 1 for an Abort station•
Channel 2 for a Manual Release station•
Channel 3 for a Supervisory device. •
Two additional input channels (zones) provide connections for “two-wire” conventional (non-relay based) smoke
and heat detectors.
Channel 4: Zone 1 detection circuit•
Channel 5: Zone 2 detection circuit•
Outputs
On the output side, three supervised outputs (1 signaling, 2 releasing) provide the following connections:
Channel 6 for a notification appliance such as a bell, horn or lamp.•
Channels 7 & 8 for a main and reserve or secondary agent release.•